Saftey issue beside replacing a 4 prong plug near a 3 prong plug on a dryer? Do i newly evacuate the ground meaningless???
Answers: You should change the pigtail (the electrics harness from the dryer to the outlet) to the 4 prong connector. Don't leave out the ground. It is in that for a purpose. 220 volts can kill you!!
to make available a good answer i requirement more info. are you replacing the cord on the dryer or are you replacing the recepticle in the wall for the dryer? you can use the prehistoric 3 wire cords to connect a dryer to an existing 3 line outlet. you can't leagally replace the recepticle in the wall beside a 3 wire part if a 4 wire section is there very soon. the three wire set up used to use the impartial as a ground, then starting next to the 1996 code a separate ground was needed.
Okay, let's see if I get this straight. You're taking a 4 prong plug off a dryer and replacing it next to a 3 prong plug so that you can plug it into a 3 prong receptacle.
In this case, you entail to hook green wire from the 3 line plug to the green terminal on the dryer and connect a #14 jumper flex from the ground terminal to the neutral terminal.
It's a total lot smarter to replace your 3 prong recepticle with a 4 prong recepticle.
I recommend you replace the 3 prong receptacle near a 4 wire component and wire it near a 4 conductor wire. You can modify things to attain it to work. But why not just do it correctly? You mentioned sanctuary and that is the use the 4 prong plug is required by code. As mentioned by freakboy. Hire an electrician to help if you are not qualified to line it.