central air problem,on split unit ,the fan at the compressor quit running .i had the fan checked it is good ?
Answers:
bad contactor not pulling in try pushing it in with a screw driver to see if the fan will run
Other answers:
recheck wire terminals, trace wires that energize fan maybe through relay or time delay ? see wire diagram
recheck wire terminals, trace wires that energize fan maybe through relay or time delay ? see wire diagram