can I raise the amperage on one circuit breaker as long as I dont exceed the max amperage on the main breaker?

I started with one A/C window unit. Everything was fine all year long. Then I add another window unit and "bam" the breaker keeps tripping and that whole side of the wall goes out. They are in seperate rooms One in the master bedroom and the added one in the living room. Well aparently they are on the same breaker because when the breaker trips they both go out along with everything on that side of the house. It's on a 15 amp, but could I raise it to a 20 amp as long as I don't exceed the 200 max recommended. Most of the things connected to this 15 amp breaker are outlets and very few ceiling lights. Besides the 2 A/C window units, there is nothing much else that's on that side of the house that are on the same circuit besides a microwave.

Answers:
Your circuit is overloaded.

The average microwave oven draws approximately 8 - 12 amps. The average window a/c units draws the same. You also need to plan for an inrush surge of current when each a/c unit is started. This inrush is typically 3 times the nameplate current rating for a couple of seconds until the motor gets up to speed.

Breakers are sized according to the wire size and load served. The smallest size wire allowed on a 15 amp circuit is 14 AWG. The smallest sized wire allowed on a 20 amp circuit is 12 AWG. If your wire is 14 AWG you may not increase the breaker size. You may find the wire size marked on the sheathing of the wire.

I would recommend installing 3 new circuits. I would put the microwave on a dedicated 20 amp circuit using 12 AWG wire and the same for each window a/c unit. If you do not feel comfortable doing this, I recommend hiring an electrician.

Other answers:
you would need to have an electrician look at your wiring to see if it is up to the increase in amps. You don't want to burn the house down
you would need to have an electrician look at your wiring to see if it is up to the increase in amps. You don't want to burn the house down
Why don't you add another breaker 15 amp, parallel to the existing one and connect the second a/c to that. You got to check with electrician for that work, because the input wiring to the existing one also needs to be checked whether it can take the extra load.
Try to find a different outlet on another circuit. Do not upgrade a breaker this way.

Likely, with a 15amp circuit, the wiring between those outlets and the panel is 14 gauge. It was intended for a few lamps and an occasional vacuum cleaner.

If you upgrade that breaker to a 20 amp, you should also upgrade the wiring to 12 gauge. Otherwise, your 14 gauge wiring could become the weaker link. You want the breaker to be the weak link so that it trips.

If you make the wire "trip" instead, it heats up... copper discolors and degrades, can melt the insulation around it, cause connections to loosen. Next thing a short happens, then sparks. And quite potentially: a fire.

Upgrading the wire is often difficult and much more effort than upgrading the wire. But it must be done.

If, by chance, you already have 12 guage wire between ALL of the points on that circuit, then I'd go for it. Turn the breaker off and determine ALL of the outlets and lights impacted. Open reach of the impacted recepticles to determine the connection sequence and wire gauge used.

While you're doing this, its a good time to re-connect any back-stabbed outlets. Often a shortcut used in 15amp circuits, is to strip a little insulation off the end of the wire and thrust it into the appropriate hold in the back of the recepticle. When you connect the 12 gauge wire, curl the stripped end and connect it to the recepticle using the side-mount srews. A much better connection.
  • I have an Admiral Signature 2000 series refrigerator. Can someone tell me where the defrost timer is located?
  • How much chlorination do you need in a spa with an ozanator?
  • i live in dallas texas and have st augistine grass/whats the best organic fertilizer to use & how often. ty?
  • what does it mean when the refrigerator compressor makes load nose when it shut down?
  • Can you get central air in an old house with no air ducks? Is it expensive?
  • Leaking fuel injector in a chevy cavalier?
  • What is the correct spark plug gap for a Wisconsin Robin W1-145 4 cycle engine?
  • i have a grease trap that is very slow, how can i clean it out. i believe it is in the fieldlin?
  • How do I get hold of rid cockroaches within my house?